Type TVR.

For the most diverse applications regarding standard volume flow rate ranges

 

Circular VAV terminal units for standard applications regarding the supply air or extract air control in variable air volume systems

  • Suitable for the control of volume flow rate, room pressure or duct pressure
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • High control accuracy even with upstream bend (R = 1D)
  • Suitable for airflow velocities up to 13 m/s
  • Closed blade air leakage to EN 1751, class 4
  • Casing air leakage to EN 1751, class C


Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type CA, CS or CF for the reduction of air-regenerated noise
  • Hot water heat exchanger Type WL and electric air heater Type EL for reheating the airflow
small_tab1_Serie TVR
  • Application
  • Description

Application

  • Circular VARYCONTROL VAV terminal units of Type TVR for the precise supply air or extract air flow control in variable air volume systems
  • Closed-loop volume flow control using an external power supply
  • For controlling, restricting, or shutting off the airflow in air conditioning systems
  • Shut-off by means of switching (equipment supplied by others)

Special features

  • Integral differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can later be measured and adjusted on site; additional adjustment device may be necessary

Variants

  • TVR: VAV terminal unit
  • TVR-D: VAV terminal unit with acoustic cladding
  • TVR-FL: VAV terminal unit with flanges on both ends
  • TVR-D-FL: VAV terminal unit with acoustic cladding and flanges on both ends
  • Units with acoustic cladding and/or a secondary silencer Type CA, CS or CF for demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted

Construction

  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)
  • A2: Stainless steel

Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Averaging differential pressure sensor for volume flow rate measurement
  • Damper blade
  • Factory-assembled control components complete with wiring and tubing
  • Aerodynamic function testing on a special test rig prior to shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy (even with upstream bend R = 1D)

Attachments

  • Easy controller: Compact unit consisting of controller with potentiometers, differential pressure transducer and actuator
  • Compact controller: Compact unit consisting of controller, differential pressure transducer and actuator
  • Universal controller: Controller, differential pressure transducer and actuators for special applications
  • LABCONTROL: Control components for air management systems

Accessories

  • G2: Matching flanges for both ends
  • D2: Lip seals on both ends (factory fitted)

Useful additions

  • Secondary silencer Type CA, CS or CF for demanding acoustic requirements
  • Heat exchanger Type WL
  • Electric air heater Type EL

Construction features

  • Circular casing
  • Spigot suitable for circular ducts to EN 1506 or EN 13180
  • Spigot with groove for lip seal
  • Position of the damper blade indicated externally at shaft extension
  • TVR-FL: Flanges to EN 12220

Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Aluminium sensor tubes
  • Plastic bearings


TVR-D

  • Acoustic cladding made of galvanised sheet steel
  • Rubber profile for the insulation of structure-borne noise
  • Lining is mineral wool


Mineral wool

  • To EN 13501, fire rating class A2, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EG

Información técnica

  • Function
  • Quick sizing
  • Specification text
  • Order code
tvr

Functional description

The VAV terminal unit is fitted with a differential pressure sensor for measuring the volume flow rate.

The control components (attachments) include a differential pressure transducer that transforms the differential pressure (effective pressure) into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller, with a Compact controller, or with individual components (Universal or LABCONTROL).

For most applications, the setpoint value comes from a room temperature controller.

The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

tvr

 

Circular VAV terminal units for variable and constant air volume systems, suitable for supply or extract air, available in seven nominal sizes.

High control accuracy (even with upstream bend R = 1D).

Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging differential pressure sensor for volume flow rate measurement and a damper blade. Factory-assembled control components complete with wiring and tubing.

Differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution)

Spigot with groove for lip seal, suitable for connecting ducts according to EN 1506 or EN 13180.

Position of the damper blade indicated externally at shaft extension.

Closed blade air leakage to EN 1751, class 4 (nominal size 100, class 2; nominal sizes 125 and 160, class 3).

Casing air leakage to EN 1751, class C.

Special features

  • Integral differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can later be measured and adjusted on site; additional adjustment device may be necessary

Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Aluminium sensor tubes
  • Plastic bearings


TVR-D

  • Acoustic cladding made of galvanised sheet steel
  • Rubber profile for the insulation of structure-borne noise
  • Lining is mineral wool


Mineral wool

  • To EN 13501, fire rating class A2, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EG

Construction

  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)
  • A2: Stainless steel

Technical data

  • Nominal sizes: 100 – 400 mm
  • Volume flow rate range: 10 to 1680 l/s or 36 to 6050 m³/h
  • Volume flow rate control range (unit with dynamic differential pressure measurement): approx. 10 to 100 % of the nominal volume flow rate
  • Differential pressure: 20 – 1500 Pa

Attachments

Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.

  • Supply voltage 24 V AC/DC
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using volt-free contacts: CLOSED, OPEN, Vmin and Vmax
  • Potentiometers with percentage scales to set the volume flow rates Vmin and Vmax
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Volume flow rate approx. 10 – 100 % of the nominal volume flow rate
  • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure

Electrical connections with screw terminals. Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller.

tvr

Compartir

Recomendar

Recomendar el contenido de esta página, mandar por mail.

Los campos marcados con un (*) sin imprescindibles de cumplimentar

Compartir

Gracias por su recomendación!

Su recomendación ha sido enviada y llegará a su destino en breve.


Contacto

Estamos aquí para atenderles

Visual contact Visual contact

Por favor mande su solicitud
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04

Los campos marcados con un (*) sin imprescindibles de cumplimentar

Contacto

Gracias por su mensaje.

Visual contact Visual contact

Su mensaje ha sido enviado correctamente, en breve será atendido.
En seguida nos pondremos en contacto con Vd.
Para información general sobre productos o servicios, por favor llamar al:
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04

Contacto

Estamos aquí para atenderles

Visual contact Visual contact

Por favor mande su solicitud
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04

Archivo adjunto (Max. 10MB)

Los campos marcados con un (*) sin imprescindibles de cumplimentar

Contacto

Gracias por su mensaje.

Visual contact Visual contact

Su mensaje ha sido enviado correctamente, en breve será atendido.
En seguida nos pondremos en contacto con Vd.
Para información general sobre productos o servicios, por favor llamar al:
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04