Type TVZ

For supply air systems with demanding acoustic requirements

 

VAV terminal units for the supply air control in buildings with variable air volume systems and demanding acoustic requirements

  • Highly effective integral attenuator
  • Box style construction for the reduction of the airflow velocity
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • Suitable for airflow velocities up to 13 m/s
  • Closed blade air leakage to EN 1751, class 4
  • Casing air leakage to EN 1751, class A


Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type TS for the reduction of air-regenerated noise
  • Hot water heat exchanger Type WT for reheating the airflow
small_tab1_Serie TVZ
  • Application
  • Description

Application

  • VARYCONTROL VAV terminal units of Type TVZ for the supply air control in variable air volume systems
  • Closed-loop volume flow control using an external power supply
  • Integral attenuator for demanding acoustic requirements
  • Shut-off by means of switching (equipment supplied by others)

Special features

  • Integral attenuator with at least 26 dB insertion loss at 250 Hz
  • Hygiene tested and certified
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can later be measured and adjusted on site; additional adjustment device may be necessary

Variants

  • TVZ: Supply air unit
  • TVZ-D: Supply air unit with acoustic cladding
  • Units with acoustic cladding and/or secondary silencer Type TS for very demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted

Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Averaging differential pressure sensor for volume flow rate measurement
  • Damper blade
  • Integral attenuator
  • Inspection access for cleaning to VDI 6022
  • Factory-assembled control components complete with wiring and tubing
  • Aerodynamic function testing on a special test rig prior to shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy (even with upstream bend R = 1D)

Attachments

  • Easy controller: Compact unit consisting of controller with potentiometers, differential pressure transducer and actuator
  • Compact controller: Compact unit consisting of controller, differential pressure transducer and actuator
  • Universal controller: Controller, differential pressure transducer and actuators for special applications
  • LABCONTROL: Control components for air management systems

Accessories

  • Lip seal (factory fitted)

Useful additions

  • Secondary silencer Type TS
  • Heat exchanger Type WT

Construction features

  • Rectangular casing
  • Spigot on the fan end suitable for circular ducts to EN 1506 or EN 13180
  • Spigot with groove for lip seal
  • Connection on the room end suitable for air duct profiles
  • Baffle plate is fitted after the damper blade for optimum aerodynamic performance
  • Position of the damper blade indicated externally at shaft extension
  • Thermal and acoustic insulation (lining)

Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Lining is mineral wool
  • Differential pressure sensor made of aluminium
  • Plastic bearings


TVZ-D

  • Acoustic cladding made of galvanised sheet steel
  • Lining is mineral wool
  • Rubber elements for the insulation of structure-borne noise


Mineral wool

  • To EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EG
  • Faced with glass fibre fabric as protection against erosion through airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth

Información técnica

  • Function
  • Technik
  • Quick sizing
  • Specification text
  • Order code
tvz

Functional description

The VAV terminal unit is fitted with a differential pressure sensor for measuring the volume flow rate.

The control components (attachments) include a differential pressure transducer that transforms the differential pressure (effective pressure) into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller, with a Compact controller, or with individual components (Universal or LABCONTROL).

For most applications, the setpoint value comes from a room temperature controller.

The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

An integral attenuator reduces the noise that is created by the restriction of the airflow.

The airflow velocity at the room end is, due to the larger rectangular cross section, about half the velocity in the circular duct.

tvz
tvz

 

Rectangular VAV terminal units for variable and constant air volume systems, suitable for supply air, available in 6 nominal sizes.

High control accuracy (even with upstream bend R = 1D).

Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging differential pressure sensor for volume flow rate measurement, a damper blade, and an integral attenuator. Factory-assembled control components complete with wiring and tubing.

Differential pressure sensor with 3 mm measuring holes (resistant to dust and pollution)

On the fan end, spigot with groove for lip seal, suitable for connecting ducts according to EN 1506 or EN 13180.

Room end suitable for the connection of air duct profiles.

Baffle plate is fitted after the damper blade for optimum acoustic and aerodynamic performance.

Casing with acoustic and thermal insulation.

Position of the damper blade indicated externally at shaft extension.

Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).

Casing air leakage to EN 1751, class B.

Complies with VDI 2083, clean room class 3, and US standard 209E, class 100. Hygiene complies with VDI 6022, DIN 1946, part 4, as well as EN 13779 and VDI 3803.

Special features

  • Integral attenuator with at least 26 dB insertion loss at 250 Hz
  • Hygiene tested and certified
  • Factory set-up or programming and aerodynamic function testing
  • Volume flow rate can later be measured and adjusted on site; additional adjustment device may be necessary

Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Lining is mineral wool
  • Differential pressure sensor made of aluminium
  • Plastic bearings


TVZ-D

  • Acoustic cladding made of galvanised sheet steel
  • Lining is mineral wool
  • Rubber elements for the insulation of structure-borne noise


Mineral wool

  • To EN 13501, fire rating class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Biosoluble and hence hygienically safe according to the German TRGS 905 (Technical Rules for Hazardous Substances) and EU directive 97/69/EG
  • Faced with glass fibre fabric as protection against erosion through airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth

Technical data

  • Nominal sizes: 125 – 400 mm
  • Volume flow rate range: 15 to 1680 l/s or 54 to 6048 m³/h
  • Volume flow rate control range (unit with dynamic differential pressure measurement): approx. 10 to 100 % of the nominal volume flow rate
  • Differential pressure: 5 – 1500 Pa

Attachments

Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.

  • Supply voltage 24 V AC/DC
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using volt-free contacts: CLOSED, OPEN, Vmin and Vmax
  • Potentiometers with percentage scales to set the volume flow rates Vmin and Vmax
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Volume flow rate approx. 10 – 100 % of the nominal volume flow rate
  • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure

Electrical connections with screw terminals. Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller.

tvz

Compartir

Recomendar

Recomendar el contenido de esta página, mandar por mail.

Los campos marcados con un (*) sin imprescindibles de cumplimentar

Compartir

Gracias por su recomendación!

Su recomendación ha sido enviada y llegará a su destino en breve.


Contacto

Estamos aquí para atenderles

Visual contact Visual contact

Por favor mande su solicitud
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04

Los campos marcados con un (*) sin imprescindibles de cumplimentar

Contacto

Gracias por su mensaje.

Visual contact Visual contact

Su mensaje ha sido enviado correctamente, en breve será atendido.
En seguida nos pondremos en contacto con Vd.
Para información general sobre productos o servicios, por favor llamar al:
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04

Contacto

Estamos aquí para atenderles

Visual contact Visual contact

Por favor mande su solicitud
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04

Archivo adjunto (Max. 10MB)

Los campos marcados con un (*) sin imprescindibles de cumplimentar

Contacto

Gracias por su mensaje.

Visual contact Visual contact

Su mensaje ha sido enviado correctamente, en breve será atendido.
En seguida nos pondremos en contacto con Vd.
Para información general sobre productos o servicios, por favor llamar al:
Tel.: +34 976 50 02 50 | Fax: +34 976 50 09 04